IRAI PERIODIC CHECK

Fire safety systems, equipment and other systems Standards and technical specifications (TS) for verification, control, maintenance
Fire extinguishers UNI 9994-1
Fire hydrant networks UNI 10779, UNI EN 671-3, UNI EN 12845
Sprinkler systems UNI EN 12845
Fire detection and alarm systems (IRAI) UNI 11224
Voice alarm systems for emergency purposes (EVAC) UNI ISO 7240-19 or UNI CEN/TS 54-32
Fire extinguishers UNI 9994-1
Smoke and heat evacuation systems UNI 9494-3
Differential pressure systems UNI EN 12101-6
Powder systems UNI EN 12416-2
Powder systems UNI EN 13565-2
Water spray systems UNI CEN/TS 14816
Water mist systems UNI EN 14972-1
Water spray systems UNI CEN/TS 14816
Condensed aerosol extinguishing system UNI EN 15276-2
Oxygen reduction systems UNI EN 16750
Fire-resistant opening doors and windows UNI 11473
Gaseous extinguishing systems UNI 11280 Series of UNI EN 15004 standards

SC10 - Alarm Buttons

Reference standards

UNI 9795:2021 Title: Fixed automatic fire detection and alarm systems - Design, installation and operation


SC11 - Smoke Detection

Reference standards

UNI EN 54-1:2021 Fire detection and fire alarm systems - Part 1: Introduction

UNI EN 54-2:2007 Fire detection and fire alarm systems - Part 2: Control and indicating panels

UNI EN 54-3:2020 Fire detection and fire alarm systems - Part 3: Fire alarm sounders

UNI EN 54-4:2007 Fire detection and fire alarm systems - Power supply equipment

UNI EN 54-5:2018 Fire detection and fire alarm systems - Part 5: Heat detectors - Point heat detectors

UNI CEN/TS 54-14:2018 Fire detection and fire alarm systems - Part 14: Guidelines for planning, design, installation, commissioning, operation and maintenance

UNI EN 54-11:2007 Fire detection and fire alarm systems – Manual call points

UNI EN 54-12:2015 Fire detection and fire alarm systems - Part 12: Smoke detectors - Linear detectors using an optical beam

UNI 9494-1:2017 Smoke and heat control systems - Part 1: Design and installation of Natural Smoke and Heat Exhaust Systems (SENFC)

UNI 9494-2:2017 Smoke and heat control systems - Part 2: Design and installation of Forced Smoke and Heat Evacuation Systems (SEFFC)UNI 9795:2010 Fixed automatic fire detection and alarm systems - Design, installation and operation

UNI 11224:2019 Initial inspection and maintenance of fire detection systems

Genera Excel e Invia WhatsApp

IMPIANTO IRAI - SORVEGLIANZA

CHECKLIST IMPIANTO IRAI - SORVEGLIANZA (Settimanale)

Selezione Descrizione verifica NOTE: ANOMALIE / DATA MANUTENZIONE
Il pulsante deve essere chiaramente visibile ed immediatamente utilizzabile
Il pulsante deve essere provvisto di cartello indicante la funzione svolta (es. allarme incendio).
Verificarne l’effettivo funzionamento; questo può essere fatto premendo il pulsante dopo aver rimosso il coperchio di protezione con un cacciavite e controllando che il suono prodotto dalla/e sirena/e sia udibile in tutto l’edificio
RIVELATORI: Verifica del corretto dialogo tra la unità di supervisione, le centrali elettroniche ed i dispositivi ad esse collegati
Controllo del software sistema di rivelazione automatica di incendio e di supervisione
Controllo delle batterie tampone e della linea di alimentazione
Eliminazione di tutte le anomalie riscontrate ricercandone le cause. Al termine del controllo non dovrà essere presente nessun tipo di guasto o anomalia a meno che la ricerca e l’eliminazione non comporti un tempo superiore alle due ore. Per tale tipo di anomalia dovrà essere avvisata immediatamente la D.L. ed essere risolta entro le 24 ore successive